MIL-PRF-52308J
added to the test fuel in accordance with API 1581, section 4.3.2.3.3 Additive Addition/Category
M Fuel.
4.4.3 Fuel temperature. Unless otherwise specified (see 4.5.4.2 and 4.5.4.3), the test fuel
temperature shall be between +40 °F to +90 °F (+5°C to +32 °C) during testing. The test fuel
temperature shall be maintained within plus or minus 11 °F (6 °C) of the starting temperature for
any individual test.
4.4.4 Test contaminants. The contaminants used, and their addition to the test fuel, shall be
in accordance with API 1581, section 4.2.3 Test Contaminants.
4.4.5 Test sampling and analysis. Test sampling and measurement shall be conducted in
accordance with API 1581, section 4.7 Test Sampling, and all subsections thereof.
4.4.5.1 Icing inhibitor. The concentration of icing inhibitor in the fuel shall be determined in
accordance with ASTM D 5006. Samples shall be taken for measurement prior to start of 4.5.3
(operational performance test), and immediately after the conclusion of such test.
6
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business