3.6.3 Element spacing. Element spacing shall meet the requirements of API/IP 1581.
3.6.4 Element mounting. Element mounts shall be installed such that removal and installation of elements does
not cause mount to rotate or loosen and a tight seal to the mounting plate is maintained. Element mounts shall have
a blunted V-type knife edge for sealing to a flat gasket on the filter-coalescer or separator. The height of the V
section shall be 0.125 inch (3 mm) +10 percent. Torque requirements for installation of elements shall be provided
as specified (see 6.2). Element mounts shall be designed to withstand 150 percent of recommended assembly torque
without permanent distortion, cracking, or failure.
3.7 Maintainability.
3.7.1 Access. Components that require regular maintenance or servicing shall be readily accessible and not
require personnel to enter the filter-separator vessel. For very large filter-separator assemblies, this may be
unavoidable. If personnel entry is required, at least two equally spaced access openings shall be provided for safe
personnel access and temporary ventilation. Filter-separators with access covers heavier than 50 pounds shall have
an integral lifting device for removal.
3.7.2 Special tools. Special tools, if required for maintenance and servicing, shall be provided with the filter-
separator assembly.
3.7.3 Case drainage. The filter design shall permit the casing to be completely drained of all fluids before
servicing and maintenance.
3.8 Environmental requirements.
3.8.1 Shock. When first article inspection is required, the filter-separator assembly shall withstand Grade A
shock requirements of MIL-S-901, without any leakage (see 4.1.1).
3.8.2 Vibration. When first article inspection is required, the filter-separator assembly shall withstand vibration
in accordance with MIL-STD-167-1, Type I Environmentally Excited (see 4.1.1).
3.8.3 Temperature variation. The filter-separator assembly shall meet the temperature variation requirements
of API/IP 1581.
3.8.4 Materials. Filter-separator materials shall meet the environmental requirements of API/IP 1581 for fuel
types in this specification (see 3.6.2).
3.9 Identification plate. Identification plates shall be provided and comply with the requirements of
API/IP 1581. Identification plates shall be visible from the location where gages are normally viewed. The
permanent identification plate shall also include the following information: MIL-PRF-15618, revision, amendment,
and date.
4. VERIFICATION
4.1 Classification of inspections. The inspection requirements specified herein are classified as follows:
a.
First article inspection (see 4.1.1).
b.
Conformance inspection (see 4.1.2).
4.1.1 First article inspection. When first article inspection is required (see 6.2), one complete filter-separator
assembly (see 3.1) shall undergo the tests and inspections outlined in Table I.
4.1.2 Conformance inspection. Each filter-separator assembly shall be inspected for conformance according to
the requirements specified in Table I.